Appendices
Appendix D - Installing Firmware Updates for the MD-BMS and MD-BMED Power Meter
93
Building Technologies
125-202
06/06/2017
Real-Time Values Screen
Click on the Real-Time Values tab at the top of the ViewPoint screen to display current
measured values.
The Real-Time Values screen shows current readings to verify that the system is
configured properly. The tables display the real-time values of Volts, Amps, Kw, KVA,
KVAR, and Power Factor (PF) for Phase L1, Phase L2, and Phase L3. This screen
also displays the CT type connected to the MD-BMS or MD-BMED Power Meter and
the CT value.
Values displayed for Volts, Amps, Kw, and so on should make sense; meaning that the
values in the table are relevant for the service being measured. This indicates the MD-
BMS or MD-BMED Power Meter setup is correct. It may also be useful to use a
handheld amp meter to test the current and compare its readings to the values
provided on the Real-Time Values screen.
To acquire new measurement values, click Update to retrieve a new set of values for
the MD-BMS or MD-BMED Power Meter. For Auto-Update, select the check box to
automatically update values approximately every 20 seconds.