BACnet Output Port Objects
Table 12: BACnet Digital Port 1 Pulse Output.
Object Identifier
Object Name
Detailed Description
13020
Port 1 output control when used as an on/off—
open/closed switch
0 = Output LOW (closed)
1 = Output HIGH (open) [default]
Object 13100 present value must = 0 to use
13100
Digital Port 1 Configuration
0 = No pulses, Port may be used as an on/off—
open/closed switch
44001 = System kWh pulses
44008 = System kVARh pulses
44011 = System kVAh pulses
13110
Port 1 Pulse Output Relay Type
0 = Normally Open (HIGH)
1 = Normally Closed (LOW)
Wiring CTs
1. Attach the CTs onto the green connectors labeled CT1, CT2, and CT3.
2. Place the CTs on the phase wires of the load to be monitored, and corresponding
to the phase of the voltage leads. The CT labeled CT1 must be placed on the L1
phase voltage load wire, CT2 must be placed on the L2 voltage load wire, and CT3
must be placed on the L3 voltage load wire.
3. See
Checking Phases, later in this section for information about the CT LEDs and
how to verify the CT installation.