ET 200 Handheld
ET 200 Handheld
Message
Possible cause
Remedy
3<=addr<=124
Invalid station number.
Key in a valid station number (3 to 124; 3 to 125 in the
case of the DP Standard slave)
or
set a valid number at the slave station.
The particular remedy always depends on the station
type.
cfg fault
Configuration error
Get in touch with your SIEMENS representative or the
manufacturer of the slave station.
The ET 200 handheld restarts.
change address
Invalid station number.
Set a valid number at the slave station.
EEPROM error
The E(E)PROM of the slave station is
defective.
Get in touch with your SIEMENS representative or the
manufacturer of the slave station.
internal error
Error in the ET 200 handheld.
Get in touch with your SIEMENS representative.
no answer
The slave station does not reply to a
frame from the ET 200 handheld.
Perform a cold restart with the slave station.
not ready
Slave station not ready for data ex-
change
Get in touch with your SIEMENS representative or the
manufacturer of the slave station.
prm fault
Faulty parameterizing message
DP Standard slave only: Compare the actual configuration
with the parameters assigned to the slave station. Check
the parameters (user parameters) you transferred with the
ET 200 handheld to the slave station.
The ET 200 handheld restarts.
prm request
Parameter error
DP Standard slave only: Use the ET 200 handheld to re-
parameterize the slave station.
The ET 200 handheld restarts.
RAM error
Error in the ET 200 handheld
Get in touch with your SIEMENS representative.
single error
The configuration of the slave station
has been changed when connecting
the ET 200 handheld.
The ET 200 handheld restarts.
If the ET 200 handheld keeps performing cold restarts, get
in touch with your SIEMENS representative or the
manufacturer of the slave station.
Error Messages
Error Messages