Dia ########
###############
Plain–text message
Set diagnostics bits
Display: STATION DIAGNOSTICS
Line 1: All bits with “1” represent a diagnostics message.
When you select the bits with the cursor, the corresponding
plain–text message is displayed in the second line.
Leaving the display: You can exit the display by pres-
sing
.
Table 9.4
Significance of plain–text messages
Message
Bit
Significance
static diag
0
1: Static diagnostics – the ET 200 hand-
held continues to request diagnostics un-
til this bit is reset by the slave station.
not ready
1
1: Station cannot be controlled yet. The
ET 200 handheld restarts.
external
diag
2
1: This bit is always set if diagnostic bits
have been reported.
not sup-
ported
3
1: Function is not supported
no load
voltage
4
1: No load voltage or output short circuit
to M (only for modules with diagnostics)
short
circuit
5
1: Output activated incorrectly (short cir-
cuit to L+; only for modules with diag-
nostics)
extdia
overflow
6
1: Overflow of diagnostics buffer
slow mode
7
1: Slave station in slow mode
ET 200U