Installation
90/214
Revision 06 • INSTALLATION AND OPERATING INSTRUCTIONS • 8DB10 • 864-5091.9
➭ Clean the sealing ring ⑥ removed from the panel connection housing, and grease it
uniformly with the supplied mounting paste (e.g. Polylub GLY 801, 0.40 kg).
➭ Insert the sealing ring ⑥ in the groove of the cover of the panel connection housing ④ .
Fig. 95:
Inserting the sealing ring
➭ Grease the contact laminations ⑬ with mounting paste Vaseline 8422 DAB 8
(order number: 8BX2091).
Fig. 96:
Greasing the socket
➭ Push the cover of panel connection housing ④ into the panel connection housing ⑤ .
Fig. 97:
Inserting the cover of the panel connection housing
NOTE
In other panel connection versions, the plug sockets may be arranged asymmetrically.
➭ If the plug sockets are arranged asymmetrically, observe the mounting direction of the
cover of the panel connection housing.