864-5091.9 • INSTALLATION AND OPERATING INSTRUCTIONS • 8DB10 • Revision 06
189/214
Operation
4
➭ Switch the three-position disconnector to CLOSED position (insert the operating lever for the DISCONNECTING function and
turn 180° clockwise).
5
➭ Remove the operating lever for the DISCONNECTING function.
The right-hand control gate in the left-hand panel returns to its initial position.
6
➭ Push the left-hand selector gate to the center position.