
Description
28/214
Revision 06 • INSTALLATION AND OPERATING INSTRUCTIONS • 8DB10 • 864-5091.9
12
Current and voltage transformers
12.1
Voltage transformers
Features
• According to IEC 60044-2
• Cast-resin insulated
• Inductive type
• Safe-to-touch due to metal enclosure
Voltage transformer types
Electrical data
Fig. 12:
Voltage transformer installation (basic scheme)
①
Busbar voltage transformer 4MT3
③
Voltage transformer 4MU4 with
three-position disconnector
②
Feeder voltage transformer 4MT7
(connection at panel connection housing)
④
Feeder voltage transformer 4MU3 (not in
the panel, connection via flexible cable with plug
size S2 at the panel connection housing, and
metal-enclosed voltage transformer)
Mounting locations
Type
Comment
Busbar
4MT3
optionally with three-position disconnector
4MU4
Panel connection
4MU3
external
4MT7
directly pluggable
Designation
4MT3
4MU4
4MT7
4MU3
Operating voltage kV
3.3 to 23.0
24.0 to 38.0
3.3 to 38.0
3.3 to 38.0
Rated voltage kV
24.0
40.5
40.5
40.5
Rated short-duration power-frequency
withstand voltage kV
65.0
95.0
95.0
95.0
Rated lightning impulse withstand voltage kV
125.0
200.0
200.0
200.0
Rated voltage factor
Un / 8h = 1.9
Un / 8h = 1.9
Un / 8h = 1.9
Un / 8h = 1.9
Un / continuous = 1.2
Un / continuous = 1.2
Un / continuous = 1.2
Un / continuous = 1.2
Standard
IEC
IEC
IEC
IEC
GOST
GOST
GOST
GOST
GB
GB
GB
GB