
864-5091.9 • INSTALLATION AND OPERATING INSTRUCTIONS • 8DB10 • Revision 06
175/214
Operation
Fig. 206: Disconnectable busbar voltage transformer
Switching operation
Switching operation is only possible if
Type
Q61 or Q62 CLOSED/OPEN
Q81 or Q82 OPEN
mechanical
Q81 or Q82 CLOSED/OPEN
Q61 or Q62 OPEN
mechanical
Additionally, electromechanical interlocks may be fitted for disconnectors and earthing switches or for earthing switches.
Fig. 207: Busbar earthing switch
Switching operation
Switching operation is only possible if
Type
Q15 or Q25 CLOSED/OPEN
opening for operating lever is open
optionally mechanical with locking device or
electromechanical
Additionally, electromechanical interlocks may be fitted for disconnectors and earthing switches or for earthing switches.