Operation
202/214
Revision 06 • INSTALLATION AND OPERATING INSTRUCTIONS • 8DB10 • 864-5091.9
43.3
Function test
Cable testing with
dismantled cable
Fig. 213: Test arrangement with dismantled cable
➭ Earth the feeder (see page 167, "Feeder earthing").
➭ Remove cable to be tested.
➭ Screw test adapter tight onto cable termination of dismantled cable.
➭ Connect test lead.
➭ Perform voltage test.
Cable testing with
connected cable
Fig. 214: Test arrangement with connected cable
➭ Earth the feeder (see page 167, "Feeder earthing").
➭ Short-circuit capacitive test sockets and test sockets on integrated voltage detecting systems
(e. g. CAPDIS).
➭ Open the circuit-breaker (see page 148, "Opening the circuit-breaker manually").
➭ Switch three-position disconnector to OPEN position
(see page 155, "Opening the three-position disconnector manually ").
➭ Screw test adapter onto cable termination.
➭ Connect test lead.
➭ Perform voltage test.
➭ After voltage test, earth the feeder (see page 167, "Feeder earthing").