Operation
200/214
Revision 06 • INSTALLATION AND OPERATING INSTRUCTIONS • 8DB10 • 864-5091.9
Earthing voltage transformers
De-earthing voltage transformers
1
Initial situation
2
➭ Push the control gate to the right.
3
➭ Switch the three-position disconnector to
READY-TO-EARTH position (insert the operating
lever for the READY-TO-EARTH function and
turn 180° clockwise).
4
➭ Remove the operating lever for
the READY-TO-EARTH function.
The control gate returns to its initial position.
1
Initial situation
2
➭ Push the control gate to the right.
3
➭ Switch the three-position disconnector to OPEN
position (insert the operating lever for the
READY-TO-EARTH function and turn
180° counter-clockwise).
4
➭ Remove the operating lever for
the READY-TO-EARTH function.
The control gate returns to its initial position.