861-9601.9 • INSTALLATION AND OPERATING INSTRUCTIONS • 8DA10 • Revision 11
37/214
Description
17.5
Classification of 8DA10 according to IEC 62 271-200
Design and construction according to IEC 62271-100
Internal arc classification according to IEC 62271-200
17.6
Standards, specifications, guidelines
Basic prescriptions and
standards
The fixed-mounted circuit-breaker switchgear 8DA10 for indoor installation complies with
the following prescriptions and standards:
DANGER
Internal arcing and explosion hazard
Will cause death, serious injury or property damage.
The switchgear may or may not be classified as arc-resistant switchgear.
If the switchgear has internal arc classification IAC A FL, the area behind the switchgear is not
tested to evaluate the effects of internal arcs.
➭ Check the information on the rating plate for the switchgear to determine
if it has an internal arc classification.
➭ Personnel must be prevented from entering the area behind the switchgear
when the switchgear is energized.
Partition class
PM (partition of metal)
Loss of service continuity category
LSC 2
Accessibility to compartments
Busbar compartment
Tool-based
Switching-device compartment Tool-based
Low-voltage compartment
Tool-based
Cable compartment
Tool-based
Designation of the internal arc classification IAC
IAC class for
- Wall-standing
arrangement
IAC A FL 40 kA, 1 s
- Free-standing
arrangement
IAC A FLR 40 kA, 1 s
Type of accessibility A
Switchgear in closed electrical service location
Access “for authorized personnel only“ according to IEC 62 271-200
- F
Front
- L
Lateral
- R
Rear (for free-standing arrangement)
Rated short-time withstand current
40 kA
Rated duration of short circuit
1 s
IEC/EN standard
VDE standard
Switchgear
8DA10
62271-1
0671-1
62271-200
0671-200
Devices
Circuit
-
breakers
62271-100
0671-100
Disconnector
62271-102
0671-102
Earthing switches
Voltage detecting systems
61243-5
0682-415
Degree of protection
IP code
60529
0470-1
IK code
62262 / 50102
0470-100
Insulation
60071
0111
Instrument transformers -
61869-1
0414-9-1
Current transformers
61869-2
0414-9-2
Voltage transformers
61869-3
0414-9-3
Installation, erection
-
61936-1 / -
0101
Insulating gas SF
6
Use and handling of SF
6
62271-4
0671-4
Specification for new SF
6
60376
0373-1
Guidelines for the checking and
treatment of SF
6
taken from
electrical equipment
60480
0373-2