Three-position disconnector
Function
The three-position disconnector combines the functions of a disconnector and an earthing
switch. The three-position disconnector is designed for no-load operation only.
Fig. 6:
Three-position disconnector with
busbar and bushing
①
Fixed contact, busbar
②
Busbar housing
③
Busbar
④
Busbar support
⑤
Fixed contact, earth
⑥
Bushing
⑦
Moving contact in
READY-TO-EARTH/EARTHED position
⑧
Moving contact in CLOSED position
⑨
Moving contact in OPEN position
Switch positions
Position indicator
Basic scheme
OPEN
- Three-position disconnector OPEN
- Circuit-breaker OPEN
CLOSED
- Three-position disconnector CLOSED
- Circuit-breaker CLOSED
READY-TO-EARTH
- Three-position disconnector READY-TO-EARTH
- Circuit-breaker OPEN
EARTHED
- Three-position disconnector EARTHED
- Circuit-breaker CLOSED