Installation
112/214
Revision 11 • INSTALLATION AND OPERATING INSTRUCTIONS • 8DA10 • 861-9601.9
➭ Insert one hexagon socket head bolt M8x25 (with pan head) each into the now free holes.
Fig. 126: Inserting hexagon socket head bolts
➭ Clean the silicone adapter and the inside-cone cast-resin bush carefully. Use a cleaning
agent without solvents and a lint-free cloth.
➭ Grease the silicone adapter and the inside-cone cast-resin bush uniformly with mounting
paste for cables sets.
➭ Lower the voltage transformer slowly onto the busbar housing.
Fig. 127: Greasing and cleaning
the silicone adapter
Fig. 128: Greasing and cleaning
the inside-cone cast-resin bush
WARNING
Risk of injury while transporting the voltage transformer
The voltage transformer may fall down during transport. Serious injury and property
damage can be the consequence.
➭ Secure the voltage transformer against falling down. If required, use a support.
➭ If necessary, transport the voltage transformer with several persons or with suitable aids.
Fig. 129: Setting down the voltage transformer
①
Lifting gear
②
Cable strap