861-9601.9 • INSTALLATION AND OPERATING INSTRUCTIONS • 8DA10 • Revision 11
19/214
Description
Operating mechanism for three-position disconnector
The three-position disconnector is operated from the switchgear front.
• Auxiliary switch
- Every operating mechanism is equipped with an auxiliary switch to indicate the switch
position.
• Motor operating mechanism
- Remote operation (standard)
- Local operation (option)
- Manual operation possible by operating lever
• Wiring
- Auxiliary switches and motor operating mechanisms are wired to terminal strips in the low-
voltage compartment.
Mechanical interlocking
Interlocking between three-position disconnector and circuit-breaker:
• If the circuit-breaker is in OPEN position, the three-position disconnector can be closed or
opened. If one of the actuating openings of the three-position disconnector is opened, the
circuit-breaker cannot be operated.
• If the circuit-breaker is in CLOSED position, no operations are possible with the three-
position disconnector.
Inserted operating lever
• If the operating lever is inserted, the circuit-breaker cannot be closed or opened.
Operation of the control gate
• The control gate can only be operated if the interrogation lever is pushed downwards.
• The corresponding operating shafts are only released at the control board after having
operated the control gate.
• The interrogation lever can only be operated if the circuit-breaker is open.
Locking device of the switching gate
The locking device of the switching gate of the three-position disconnector can be padlocked
in all three switch positions.
Electrical interlocking
For information about the electrical interlocks, see the supplied circuit diagrams.
Holding the control gate on the left
Control gate in the center
Holding the control gate on the right
Three-position disconnector can be closed or
opened
No switching operation possible
Ready-to-earth/earthing is possible
READY-TO-EARTH function is blocked
DISCONNECTING and READY-TO-EARTH functions
are blocked
DISCONNECTING function is blocked