Connecting and installing RS485 interfaces
Serial Interfaces of MOVIDRIVE® B
• DOP11B operator terminal
Electrical
isolation
• The serial interface XT is not electrically isolated. It must be used for point-to-point
connections only.
Terminating
resistor
• Matching terminating resistors are integrated in all SEW components.
Cable length
• Maximum cable length: 3 m (5 m for shielded cables)
Baud rate
• The baud rate for RS485 communication is set using DIP switch S13 (on the front of
MOVIDRIVE
®
B beneath the XT socket).
The set baud rate takes effect once the DIP switch position has been changed.
64282AXX
MOVIDRIVE
®
B
DOP11B
PCS21A
TIP
The DBG60B, UWS21B and USB11A options are connected to the XT socket. The
options cannot be used at the same time.
Baud rate
DIP switch S13
9.6 kBaud
ON
57.6 kBaud
1)
1) Factory setting
OFF