System Manual – MOVITRAC® 07
Explanation of the parameters
Parameters
802
•
Factory setting
yes / YES (perform factory setting)
no / NO (do not perform factory setting)
- / (Delivery condition)
Setting
P803 Parameter lock = ON enables you to prevent any changes to parameters. This does not apply to P840
Manual reset and P803 itself. The parameter lock makes sense, for example, after the MOVITRAC
®
07 settings have
been optimized. You can enable parameter changes again by setting
P803 Parameter lock = OFF.
The parameter lock also works for parameter changes via the RS-485 and SBus interfaces.
803
•
Parameter lock
off / OFF (all parameters can be changed)
on / ON (only P803 and P840 can be changed)
P804 Reset statistic data permits the statistical data stored in the EEPROM (fault memory) to be reset. The factory set-
ting function does not affect these data. The parameter automatically reverts to NO after the reset is finished.
804
Reset statistic data
NO (no reset is performed)
FAULT MEMORY (the content of the fault memory is reset)
81_
Serial communication (refer to the MOVITRAC
®
07 Communication manual for more information) You are
not allowed to change these parameters while an IPOS program is running.
810
•
RS485 address (only for ser-
vice purposes)
Setting range 0 ... 99
P810 sets the address of the MOVITRAC
®
07 for communication via the
serial interface.
On delivery, the MOVITRAC
®
07 address is always 0. SEW-EURODRIVE
recommends not using address 0, in order to prevent data transfer collisions
when serial communication is used with several inverters.
811
RS-485 group address (only
for service purposes)
Setting range 100 ... 199
The group address must be set to 100.
812
RS485 timeout delay (only
for service purposes)
Setting range 0 ... 650 [s]
P812 must be set to 0.
813
•
SBus address
Setting range 0 ... 63
P813 sets the system bus address of MOVITRAC
®
07. The MOVITRAC
®
07 can communicate with a PC, PLC or MOVIDRIVE
®
, for example, using
the system bus with this address.
On delivery, the MOVITRAC
®
07 address is always 0. SEW-EURODRIVE
recommends not using address 0, in order to prevent data transfer collisions
when serial communication is used with several inverters.
814
SBus group address
Setting range 0 ... 63
P814 makes it possible to group together several MOVITRAC
®
07 units for
communication via the SBus interface. All MOVITRAC
®
07 units with the
same SBus group address can thus be addressed using a multicast tele-
gram via this address. The data received via the group address are not
acknowledged by MOVITRAC
®
07. For example, the SBus group address
makes it possible to send setpoint selections to a group of MOVITRAC
®
07
inverters simultaneously. An inverter with group address 0 is not assigned to
any group.
No.
OP Name
Description
P6..
P60.
P600