ND line chokes
Technical Data
Dimensions ND 020-013 / ND 027-123 / ND 035-073 / ND 085-013 / ND 1503
Several inverters on one line choke
•
The supply system contactor must be designed for the total current.
•
The fuse must correspond to the rated current value of the line choke.
•
Connect MOVITRAC
®
07 frequency inverters with identical configurations to the line
chokes.
05250AXX
Figure 38: Dimensions ND 020-013 / ND 027-123 / ND 035-073 / ND 085-013 / ND 1503 with [1] space for modular terminal
blocks with touch guard
Type
Main dimensions [mm (in)]
Fixing dimensions [mm (in)]
Weight [kg (lb)]
A
B
C
a
b
d/e
ND 020-013
85 (3.4)
60 (2.4)
120 (4.7)
50 (2.0)
31 (1.2)
5 - 10 (0.2 - 0.4)
0.5 (1.1)
ND 027-123
185 (7.3)
175 (6.9)
120 (4.7)
136 (5.4)
87 (3.4)
5 - 10 (0.2 - 0.4)
6.0 (13.2)
ND 035-073
185 (7.3)
200 (7.9)
120 (4.7)
136 (5.4)
87 (3.4)
5 - 10 (0.2 - 0.4)
11 (24.2)
ND 045-013
125 (4.9)
95 (3.7)
170 (6.7)
84 (3.3)
55 ... 75 (2.2 ... 3.0)
6 (0.2)
2.5 (5.5)
ND 085-013
185 (7.3)
115 (4.5)
235 (9.3)
136 (5.4)
56 (2.2)
7 (0.3)
8 (17.6)
ND 1503
255 (10.0)
140 (5.5)
230 (9.1)
170 (6.7)
77 (3.0)
8 (0.3)
17 (37.5)
P
i
f
kVA
Hz
n