UL compliant installation
Installation
8.2
UL compliant installation
Please note the following points for UL compliant installation:
•
Only use copper cables with the following temperature ranges as connection leads:
– For MOVITRAC
®
07 ... Temperature range 60/75 °C.
•
Necessary tightening torques of MOVITRAC
®
07 power terminals: See installation
notes.
•
The inverters are only allowed to be operated on supply systems with a maximum
phase-to-earth voltage of 300 V
AC
.
•
The inverter is only allowed to be operated on IT systems if: The phase-to-earth volt-
age of 300 V
AC
cannot be exceeded either during operation or in case of a fault.
•
The MOVITRAC
®
07 frequency inverter is only allowed to be operated on supply sys-
tems which can supply maximum values in accordance with the following table. The
performance data of the fuses must not exceed the values in the following table.
Maximum values / fuses
230 V units
400/500 V units
MOVITRAC
®
07
Max. supply
current
Max. supply voltage
Fuses
004/005/008/011/015/022
5000 A
AC
240 V
AC
35 A / 250 V
037
5000 A
AC
240 V
AC
30 A / 250 V
055/075
5000 A
AC
240 V
AC
30 A / 250 V
110
5000 A
AC
240 V
AC
175 A / 250 V
150
5000 A
AC
240 V
AC
225 A / 250 V
220/300
10000 A
AC
240 V
AC
350 A / 250 V
MOVITRAC
®
07
Max. supply cur-
rent
Max. supply voltage
Fuses
005/008/011
5000 A
AC
500 V
AC
15 A / 600 V
015/022/030/040
5000 A
AC
500 V
AC
30 A / 600 V
055/075
10000 A
AC
500 V
AC
30 A / 600 V
110
10000 A
AC
500 V
AC
30 A / 600 V
150/220
5000 A
AC
500 V
AC
175 A / 600 V
300
5000 A
AC
500 V
AC
225 A / 600 V