Technical data of MOVITRAC® 07
Technical Data
Provide 100 mm (4 in) clearance above and below the unit to ensure adequate cooling!
There is no need for clearance at the sides. You can line up the units directly next to one
another. Make sure that the circulation of air is not disrupted by cables or other installa-
tion materials. Prevent the heated exhaust air from other units from blowing onto this
unit.
GENERAL
Power loss at I
N
P
V
75 W
100 W
125 W
Current limitation
125 % I
N
continuous duty (fan/pump operation)
150 % I
N
for maximum 60 seconds
PWM frequency
f
PWM
4 / 8 / 12 / 16 kHz
Speed range
Resolution
n
A
∆
n
A
0 ... 5500 rpm
1 rpm
Connections
Terminals 4 mm
2
Dimensions
W x H x D
90 x 295 x 150 mm
3.5 x 9.5 x 5.9 in
Weight
m
2.5 kg
5.5 lb
MOVITRAC
®
MC07A (1-phase supply system)
011-2B1-4-..
015-2B1-4-..
022-2B1-4-..
05805AXX
Figure 7: Dimensions, MOVITRAC
®
07 size 0L
P
i
f
kVA
Hz
n