344
Manual – IPOSplus®
23
Set commands
Assembler – Commands
Example 2
The following example illustrates the principle of this process:
M0 :SETINTERROR M01
JMP UNCONDITIONED , M0
M01 :ADD H0 + 1
RET
END
H0 counts up as long as the unit error still occurs. After the fault reset, H0 contains the
value from the EEPROM, for example, 0. The value from the working memory calculated
during the error is lost
23.8.4 SETSYS
The SETSYS command writes the value of one or more variables to an internal system
value. The first argument selects the system value to be written whilst the second argu-
ment contains the number of the (first) source variable.
The system values are reset to their original values when the system is switched off
(mains and 24 V power).
INFORMATION
Writing system values can alter unit settings that have been made for the application
during startup. In particular, changes to positioning ramps and the maximum current
must be adapted to the features of the system to preclude the risk of damage and haz-
ards (e.g. due to mechanical overload).