Special unit commands
Assembler – Commands
Example 2
As an alternative to the example above, a program branch (jump flag M100) can be ex-
ecuted when the touch probe position is reached. This is achieved using the "SETINT
TOUCHP1 M100" command.
WDOFF/WDON /
WATCH DOG
OFF/ON
The watchdog is called up in the time interval specified in the argument. All tasks are
halted and the drive is stopped with fault 41 if the time specified in the watchdog timer
H490 elapses before the monitoring function is switched off using the WDOFF com-
mand. (The output stage is inhibited and the brake is applied. The drive coasts to a halt
if there is no brake.)
Structure
516742923
Command structure
Mxxx WDON X1
Mxxx WDOFF
Mxxx: Label
(optional)
X1:
Interval in ms in which the watchdog is called up.