292
Manual – IPOSplus®
22
Binary inputs/outputs
Assembler – Programming
Query via system
variable
The terminal level of the binary inputs in the basic unit and any installed option are rep-
resented cyclically in the system variables
H483 INPUT LVL
(MOVIDRIVE
®
A) /
H520
INPUT LVL B
(MOVIDRIVE
®
B). In the process, the bits of the H483 system variable
are each assigned to one hardware input.
The assignment of the H483 system variables for MOVIDRIVE
®
A / H520 for
MOVIDRIVE
®
B to the binary input terminals in described in the section "IPOS
plus®
Vari-
ables / Overview of the system variables".
The binary inputs in the IPOS
plus®
program can be queried using the value of the vari-
ables H483/H520. This is useful for querying inputs to be used to transfer a binary-
coded, for example, for selecting a table position.
Binary terminals represented with the higher value bits of variables H483/H520 can also
be queried using a combination of the BMOV and JMP commands. This is the case
when two options are installed at the same time with terminal expansion.
Table 3: Example of transmitting a binary-coded value via input terminals of MOVIDRIVE
®
A
Example: Reading inputs
Unit's binary inputs
Terminal designation
DI05
DI04
DI03
DI02
DI01
DI00
Significance
2
5
2
4
2
3
2
2
2
1
2
0
Terminal level
1
0
0
0
1
1
Evaluation
1 × 2
5
0 × 2
4
0 × 2
3
0 × 2
2
1 × 2
1
1 × 2
0
Variable value H483
1)
1) If all DIO11A/DIP11A input terminals and control word 2 are set to level "0".
32 + 0 + 0 + 0 + 2 + 1 = 35