94
Operations Switched PDU
Installation and Operations Manual
Adding an infeed to a UPS:
The Set UPS AddInfeed command adds a logical association of an infeed to a UPS.
To add an infeed to a UPS:
At the Switched CDU: prompt, type
set ups addinfeed
and press
Enter
.
At the prompt, enter the index number for the UPS record to be changed and press
Enter
.
At the prompt, type the absolute infeed ID of the desired infeed, and press
Enter
.
Example
The following command associates infeed .aa to UPS record at index number 1:
Switched CDU: set ups addinfeed<Enter>
UPS UPS Infeed
Index Type IDs
1 Liebert
2 MGE .AA
Select UPS(1-8): 1<Enter>
Infeed ID: .aa<Enter>
Removing an infeed from a UPS:
The Set UPS DelInfeed command removes a logical association of an infeed from a UPS.
To remove an infeed from a UPS:
At the Switched CDU: prompt, type
set ups delinfeed
and press
Enter
.
At the prompt, enter the index number for the UPS record to be changed and press
Enter
.
At the prompt, type the absolute infeed ID of the desired infeed, and press
Enter
.
Example
The following command removes the association of infeed .aa from UPS record at index number 2:
Switched CDU: set ups addinfeed<Enter>
UPS UPS Infeed
Index Type IDs
1 Liebert .AA
2 MGE .AA
Select UPS(1-8): 2<Enter>
Infeed ID: .aa<Enter>