SNMP Traps
The Switched PDU supports five types of SNMP traps. Traps are enabled at the Tower (T), Infeed (I), outlet (O),
Environmental Monitor (E) or sensor (S) level.
Trap Summary
Name
Level(s)
Description
Status
T, I, O, E, S
Operational status change
Change
O
Control status change
Load
I
Input load out of limit
Temp
S
Temperature is out of range
Humid
S
Relative Humidity is out of range
All traps include the location of the PDU as defined with the Set Location command.
Status trap
A Status trap is generated when an error condition occurs on a tower, infeed, Environmental Monitor or individual
sensor. Status traps include the reported status, the location of the PDU, and identifier/name of the affected tower,
infeed, outlet, environmental monitor, or sensor.
Any error state generates a Status trap and triggers the trap timer. A new trap is generated at the end of every timer
period until the Status returns to a non-error status. All status traps are enabled by default.
Tower Status Traps
Status
Error
Description
Normal
Tower is working correctly
NoComm
x
Communication to the tower has been lost
Infeed Status Traps
Status
Error
Description
On
Infeed is on
OffError
x
Infeed should be on but no current is sensed at the infeed
NoComm
x
Communication to the infeed has been lost
Outlet Status Traps
Status
Error
Description
On
Outlet is on
Off
Outlet is off
OnWait
Outlet Status in transition
OffWait
Outlet Status in transition
OnError
x
Outlet should be off but current is sensed at the outlet
OffError
x
Outlet should be on but no current is sensed at the outlet
OffFuse
x
Outlet should be on but a blown fuse has been detected
OnFuse
x
Outlet should be on but a blown fuse has been detected downstream
NoComm
x
Communication to the outlet has been lost
Environmental Monitor Status Traps
Status
Error
Description
Normal
Environmental Monitor is working correctly
NoComm
x
Communication to the Environmental Monitor has been lost