Switched PDU
Installation and Operations Manual
Operations
89
Testing the FTP upload configuration:
The Set FTP Test command validates that the PDU can login to the FTP server and verify/download the firmware
file.
To test the FTP upload configuration:
At the Switched CDU: prompt, type
set ftp test
, and press
Enter
.
Displaying FTP configuration information:
The Show FTP command displays all FTP configuration information.
FTP Host IP address
FTP Host username and password
Firmware filepath and filename
Configuration of automatic updates
To display FTP configuration information:
At the Switched CDU: prompt, type
show ftp
and press
Enter
.
Example
The following command displays the FTP configuration information:
Switched CDU: show ftp<Enter>
FTP Configuration
Host: 10.1.2.100
Username: djones
Password: *******
Directory: /firmware/7.0d
Filename: smcdu-v70d.bin
FTP Automatic Updates Configuration
Automatic Updates: Disabled
Scheduled Day: Everyday
Scheduled Hour: 1 PM
SNTP Administration
The firmware supports the use of a network time service to provide a synchronized time reference.
About Daylight Saving Time (DST)
Support for DST is disabled by default. When enabled, the date and time are automatically adjusted forward one hour
between the starting and ending dates and times (which can be configured).
NOTE:
If Daylight Saving Time (DST) is enabled, all system time displays will be shown with the current DST start/end date/time settings.
The default time zone is set for the United Stated until at least 2015.
The time zone format is:
mo.w.d/h:m:s
, as follows:
mo
= month from January to December (1-12)
w
= week number (1-4) or the last week (5)
d
= day of week from Sunday to Saturday (0-6)
h
= hour (0-23)
m
= minute (0-59)
s
= second (0-59)