Switched PDU
Installation and Operations Manual
Operations
81
Enabling or disabling the Cisco EnergyWise network:
NOTE:
Only commands through the CLI are supported for the Cisco EnergyWise network. There is no firmware web-based interface for
EnergyWise. Enabling EnergyWise requires a system restart.
The Set EnergyWise command enables or disables the EnergyWise network support:
To enable or disable EnergyWise:
At the Switched CDU: prompt, type
set energywise
, followed by
enabled
or
disabled
, and press
Enter
.
Example
Switched CDU: set energywise enabled
Command successful –- restart required
Setting up PDUs in the Cisco EnergyWise network:
NOTE:
To use EnergyWise, you must first configure domain name, port, and secret.
The Set EnergyWise Domain command configures the EnergyWise domain the PDU belongs to. The limit of the Domain
Name is 64 characters.
To set the EnergyWise domain name:
At the Switched CDU: prompt, type
set energywise domain
, followed by the domain name, and press
Enter
.
Example
Switched CDU: set energywise domain 10.1.2.120
Command successful
To set the EnergyWise port:
The default port number is 43440; the valid range for port numbers is 1-65535.
At the Switched CDU: prompt, type
set energywise port
, followed by the port number, and press
Enter
.
Example
Switched CDU: set energywise port
Port [666]: 700
Command successful
To set the EnergyWise secret:
The limit of the Secret field is 64 characters. A blank secret is also acceptable.
At the Switched CDU: prompt, type
set energywise secret
, then verify the secret, and press
Enter
.
Example
Switched CDU: set energywise secret
Secret: ********
VerifySecret: ********
Command successful