Switched PDU
Installation and Operations Manual
Advanced Operations
111
Humidity Trap
The Humidity trap is generated whenever the humidity on a temperature/humidity sensor is beyond preset thresholds.
Humidity traps include the reported relative humidity, humidity status, location of the PDU, and identifier and name
of the affected sensor.
Any error state generates a Humidity trap and triggers the trap timer. A new trap is generated at the end of every timer
period until the Humidity returns to a non-error status.
Humidity traps
Status
Error
Description
Normal
The sensor is working correctly and the relative humidity is within preset thresholds
NotFound
No sensor has been detected
Reading
Humidity status currently being read
HumidLow
x
Relative humidity at the sensor below preset low threshold
HumidHigh
x
Relative humidity at the sensor exceeds preset high threshold
ReadError
x
Unable to read Humidity status
Lost
x
Sensor initially detected but communication to the sensor has been lost
NoComm
x
Communication to the sensor has been lost
Configuring Traps
SNMP Trap Command Summary
Command
Description
Set Trap Tower Status
Enables or disables the Tower Status trap
Set Trap Infeed Status
Enables or disables the Infeed Status trap off
Set Trap Infeed Load
Enables or disables the Infeed Load trap
Set Trap Infeed Highthresh
Sets the Infeed Load trap high limit
Set Trap Outlet Change
Enables or disables the Outlet Change trap
Set Trap Outlet Status
Enables or disables the Outlet Status trap
Set Trap EM Status
Enables or disables the Environmental Monitor Status trap
Set Trap THS Status
Enables or disables a temperature/humidity sensor Status trap
Set Trap THS Temp
Enables or disables a temperature/humidity sensor Temp trap
Set Trap THS Tempdelta
Sets temperature recovery delta
Set Trap THS Temphigh
Sets a temperature/humidity sensor Temp trap high limit
Set Trap THS Templow
Sets a temperature/humidity sensor Temp trap low limit
Set Trap THS Humid
Enables or disables a temperature/humidity sensor Humid trap
Set Trap THS Humiddelta
Sets humidity recovery delta
Set Trap THS Humidhigh
Sets a temperature/humidity sensor Humid trap high limit
Set Trap THS Humidlow
Sets a temperature/humidity sensor Humid trap low limit
Show Traps
Displays trap configurations