Switched PDU
Installation and Operations Manual
Operations
77
Displaying system configuration information:
The Show System command displays all system configuration information.
Firmware version
NIC module serial number and MAC address
Hardware revision code and Flash size
Uptime since last system restart
System location description
Area (footprint) and power factor
3-phase load out-of-balance threshold and alert status
To display system configuration information:
At the Switched CDU: prompt, type
show system
and press
Enter
.
Example
System Information
F/W Version: Sentry Version 6.0a
NIC S/N: 1600001
MAC Address: 00-0a-9c-10-00-01
H/W Rev Code: 0
Flash Size: 2 MB
Uptime: 0 days 6 hours 14 minutes 1 second
Location: Florida HQ
Area <Footprint>: 6.3 square feet
Power Factor: 0.80
3-Phase Load Out-of-Balance
Threshold: 20 percent
Alerting: Enabled
Displaying system power status:
The System Status command displays system power and tower information.
To display system power status:
At the Switched CDU: prompt, type
sysstat
and press
Enter
.
Example
Switched CDU: sysstat
System Power Status
Total Power Consumption: 170 Watts
Area <Footprint>: 100.0 Square Meters
Watts Per Area Unit: 2 Watts Per Square Meter
Tower Status
Tower Tower Tower
ID Name Status
.A TowerA Normal
.B TowerB Normal
Command successful
NOTE:
For 3-phase systems, if the Out-of-Balance Alerting feature is enabled, and the system goes into a load out-of-balance condition,
the System Status command will display the alert “3ph Out-of-Balance” in the Tower Status section, unless there is a higher priority tower
error state to report.