Alarms and faults
This menu can also be called directly by pressing the flashing
“Alarms
” and
“Faults
” keys on the upper band.
This screen allows the user to view the list of faults present on the installation.
The first two columns give details of the date and time that the fault appeared.
The
“Status
”
column indicates whether the fault is still present
“1”
, or not present
“0”
.
The “
@”
column gives the address of the variable associated with the fault.
The
“Text
” column identifies the type of fault.
A line with a red background characterises a fault and a line with an orange background characterises an alarm.
Navigation reference: 1.6
15/07/09
19 :10 :00
GS 1
Alarms & Faults
Stop
Faults
Alarms
Date
Time
Status
@
Title
26/11/03
11:11:12’55
1
6131
HT LOW COOLANT LEVEL FAULT
26/11/03
10:35:16’28
0
6017
INSULATION 1 ALARM
26/11/03
10:10:10’10
0
60C3
CIRCUIT BREAKER FAULT ON GENERATING SET
OUTPUT
-1-
Function keys
-2-
Synchro. column
-3-
Central unit measure.
summary
To clear a fault, it is necessary to:
check that the fault has disappeared (status
0
) and whether it is necessary to eliminate its causes
select the line in question; the text on the line is displayed in white
press
the
“Reset”
key on the keypad; the line is deleted.
When a fault is displayed, its effect on the operation remains active even if its cause has disappeared.
When in Manu or Auto mode, if the user wants to clear a fault with a "stopped" clearance mode, a screen
will inform the user to switch to stop mode.
Important
Keys for scrolling when the list is longer than the number
of lines possible on the screen, i.e. 4 lines
Active line
92/297
Summary of Contents for R570U
Page 1: ...User and maintenance manual for generating sets R570U 33504081501NE_1_1 ...
Page 15: ...Alternator Cabinet Figure 1 3 Examples of identification plates 13 297 ...
Page 18: ...Sockets voltage 208 120V 16 297 ...
Page 125: ...9 Appendix 9 1 Appendix A Engine user and maintenance manual 123 297 ...
Page 126: ...124 297 ...
Page 128: ...126 297 ...
Page 129: ...OPERATOR S MANUAL Generating set and industrial engines 16 liter EMS 2 127 297 ...
Page 159: ...157 297 ...
Page 218: ...216 297 ...
Page 220: ...218 297 ...
Page 222: ...7748681 English 12 2011 220 297 ...
Page 223: ...9 2 Appendix B Alternator user and maintenance manual 221 297 ...
Page 224: ...222 297 ...
Page 226: ...224 297 ...
Page 250: ...www leroy somer com 248 297 ...
Page 261: ...Installation and maintenance R250 A V R 4067 en 2009 05 b LEROY SOMER 11 259 297 ...
Page 281: ...2012 03 e LEROY SOMER 19 Installation and maintenance R 450 AVRs 4531 en 279 297 ...
Page 282: ...www leroy somer com 280 297 ...