9. After return to the KERYS home screen,
The configuration will only be taken into account if the following operations are carried out:
Turn on the battery isolator switch.
Wait 5 seconds.
Turn off the battery isolator switch.
Important
Power plant Without common part and without inverter (A632-A633)
1. Turn off the battery isolator switch.
2. Check that the emergency stop buttons are activated.
3. Press the “STOP” button on the KERYS.
4. Turn the changeover switch to position
2.
1: SOLO GENERATING SET WITHOUT GRID COUPLING
APPLICATION:
A612
2: PRODUCTION POWER PLANT WITHOUT GRID COUPLING
APPLICATION:
A632 / A633
3: NOT APPLICABLE
4 : SOLO GENERATING SET WITH GRID COUPLING
APPLICATION:
A651
(If the switch is already set to “
2
”, turn the switch and return to position ‘’
2
’’)
After changeover, the screen below appears.
Choix configuration centrale loueur
A632: Power plant without shared switching unit without Normal/Emergency parallel line
A633: Power plant without shared switching unit without Normal/Emergency Digital Bus
5. Select the configuration “
A632: Power plant without shared switching unit without Normal/Emergency parallel line”
by
directly clicking on the touch screen.
Select the configuration “
A633: Power plant without shared switching unit without Normal/Emergency Digital Bus”
by clicking
directly on the touch screen.
N.B. selecting detection depends on the connection made according to Section 5. “Connections of
the generating sets”.
Important
1
4
3
2
98/297
Summary of Contents for R570U
Page 1: ...User and maintenance manual for generating sets R570U 33504081501NE_1_1 ...
Page 15: ...Alternator Cabinet Figure 1 3 Examples of identification plates 13 297 ...
Page 18: ...Sockets voltage 208 120V 16 297 ...
Page 125: ...9 Appendix 9 1 Appendix A Engine user and maintenance manual 123 297 ...
Page 126: ...124 297 ...
Page 128: ...126 297 ...
Page 129: ...OPERATOR S MANUAL Generating set and industrial engines 16 liter EMS 2 127 297 ...
Page 159: ...157 297 ...
Page 218: ...216 297 ...
Page 220: ...218 297 ...
Page 222: ...7748681 English 12 2011 220 297 ...
Page 223: ...9 2 Appendix B Alternator user and maintenance manual 221 297 ...
Page 224: ...222 297 ...
Page 226: ...224 297 ...
Page 250: ...www leroy somer com 248 297 ...
Page 261: ...Installation and maintenance R250 A V R 4067 en 2009 05 b LEROY SOMER 11 259 297 ...
Page 281: ...2012 03 e LEROY SOMER 19 Installation and maintenance R 450 AVRs 4531 en 279 297 ...
Page 282: ...www leroy somer com 280 297 ...