4.5.1 - Checking the winding
You can check the winding insulation by
performing a high voltage test. In this case,
you must disconnect all AVR wires.
Damage caused to the AVR in such
conditions is not covered by our
warranty.
4.5.2 - Checking the diode bridge
A diode in good working order should allow
the current to flow only in the anode-to-
cathode direction.
C
A
A n o d e
C a t h o d e
-
-
+
+
~
~
~
C C C
A A A
C C C
A A A
~ ~ ~
-
C
A
+
-
C
A
+
4.5.3 - Checking the windings and
rotating diodes using separate
excitation
During this procedure, make sure that
the alternator is disconnected from any
external load and inspect the terminal
box to check that the connections are
fully tightened.
1) Stop the unit, disconnect and isolate the
AVR wires.
2) There are two ways of creating an
assembly with separate excitation.
Assembly A:
Connect a 12 V battery in
series with a rheostat of approximately
50 ohms - 300 W and a diode on both exciter
field wires (5+) and (6-).
6 -
5 +
Diode 1A
12V battery
Rh. 50
Ω
-300W
-
+
ASSEMBLY A
Exciter field
Assembly B:
Connect a “Variac” variable
power supply and a diode bridge on both
exciter field wires (5+) and (6-).
Both these systems should have
characteristics which are compatible with
the field excitation power of the machine
(see the nameplate).
3) Run the unit at its rated speed.
4) Gradually increase the exciter field
current by adjusting the rheostat or the
variac and measure the output voltages on
L1 - L2 - L3, checking the excitation voltage
and current at no load (see the machine
nameplate or ask for the factory test report).
When the output voltage is at its rated value
and balanced within 1% for the rated
excitation level, the machine is in good
working order. The fault therefore comes
from the AVR or its associated wiring (ie.
sensing, auxiliary windings).
Diode 1A
-
+
6 -
5 +
Variac
AC
220V
DC
12V
50
60
70
80
90
100
40
30
20
10
0
ASSEMBLY B
Exciter field
WARNING
237/297
Summary of Contents for R570U
Page 1: ...User and maintenance manual for generating sets R570U 33504081501NE_1_1 ...
Page 15: ...Alternator Cabinet Figure 1 3 Examples of identification plates 13 297 ...
Page 18: ...Sockets voltage 208 120V 16 297 ...
Page 125: ...9 Appendix 9 1 Appendix A Engine user and maintenance manual 123 297 ...
Page 126: ...124 297 ...
Page 128: ...126 297 ...
Page 129: ...OPERATOR S MANUAL Generating set and industrial engines 16 liter EMS 2 127 297 ...
Page 159: ...157 297 ...
Page 218: ...216 297 ...
Page 220: ...218 297 ...
Page 222: ...7748681 English 12 2011 220 297 ...
Page 223: ...9 2 Appendix B Alternator user and maintenance manual 221 297 ...
Page 224: ...222 297 ...
Page 226: ...224 297 ...
Page 250: ...www leroy somer com 248 297 ...
Page 261: ...Installation and maintenance R250 A V R 4067 en 2009 05 b LEROY SOMER 11 259 297 ...
Page 281: ...2012 03 e LEROY SOMER 19 Installation and maintenance R 450 AVRs 4531 en 279 297 ...
Page 282: ...www leroy somer com 280 297 ...