8.4. Load
preconization
Highly discharged or sulphated batteries (formation of whitish lead sulphate deposit on the plates, which becomes hard and
insoluble to acid; this deposit reduce the active surface of the plates, and increases their internal resistance) can no longer
regenerate or be charged in a generating set.
A discharged battery should be recharged immediately, or else it will suffer irreparable damage.
Important
Battery
charge
When several batteries are connected together, the following points should be checked:
Are the batteries connected in series?
Has the correct voltage been chosen? 1 battery x 12 V , 3 x 36V batteries.
Adjust the charge current to the lowest battery.
The power difference between the batteries must be as low as possible.
Example of charge:
12V 60 Ah battery = charging current 6 A.
Charge status: 50% (acid density 1.21/voltage when idle 12.30V).
The battery is short 30 Ah, and this must be recharged.
Charge factor: 1.2.
Ah x 1.2 = 36 Ah to be charged.
Charging current: 6A approximately 6 hours charging required.
Recharging is complete when the battery voltage and the acid density stop increasing.
→
The charging current must always be 1/10
th
of the nominal capacity of the battery.
The power of the charger must be suitable for the battery to be charged and the charging time available.
You need to use an automatic charger able to provide a sufficient voltage and charging current, as well as a compensation voltage to
handle spontaneous battery discharge.
121/297
Summary of Contents for R570U
Page 1: ...User and maintenance manual for generating sets R570U 33504081501NE_1_1 ...
Page 15: ...Alternator Cabinet Figure 1 3 Examples of identification plates 13 297 ...
Page 18: ...Sockets voltage 208 120V 16 297 ...
Page 125: ...9 Appendix 9 1 Appendix A Engine user and maintenance manual 123 297 ...
Page 126: ...124 297 ...
Page 128: ...126 297 ...
Page 129: ...OPERATOR S MANUAL Generating set and industrial engines 16 liter EMS 2 127 297 ...
Page 159: ...157 297 ...
Page 218: ...216 297 ...
Page 220: ...218 297 ...
Page 222: ...7748681 English 12 2011 220 297 ...
Page 223: ...9 2 Appendix B Alternator user and maintenance manual 221 297 ...
Page 224: ...222 297 ...
Page 226: ...224 297 ...
Page 250: ...www leroy somer com 248 297 ...
Page 261: ...Installation and maintenance R250 A V R 4067 en 2009 05 b LEROY SOMER 11 259 297 ...
Page 281: ...2012 03 e LEROY SOMER 19 Installation and maintenance R 450 AVRs 4531 en 279 297 ...
Page 282: ...www leroy somer com 280 297 ...