6.3.4.3.
Configuration in solo generating set
Without Normal/Emergency inverter (A612)
This configuration is designed to provide:
The generation of electricity for an installation from an external starting command (dry contact).
The generation of electricity for an installation in forced operation.
Regulation
module
Base
module
C
A
N
B
us
E
th
e
rn
e
t
3PH + N
3PH
M
MMI module
Application (load)
Automatic operation (Kerys in “AUTO” mode)
Loss of grid voltage
•
Generating set start request (dry contact, switch, clock, etc.).
•
The speed and voltage of the generating set increase.
•
Generating set power unit switched off after voltage and frequency stabilisation.
Return of grid voltage
•
Dry contact, switch, clock, etc. switched on.
•
Cooling
delay.
•
Generating set stopped and set to standby.
FORCED OPERATION (Kerys in “AUTO” mode)
Start of FORCED OPERATION
•
Generating set start request (dry contact, switch, clock, etc.).
•
The speed and voltage of the generating set increase.
•
Generating set power unit switched off after voltage and frequency stabilisation.
The installation is supplied by the generating set
End of FORCED OPERATION
•
Dry contact, switch, clock, etc. switched on.
•
Generating set power unit switched on.
•
Cooling
delay.
•
Generating set stopped and set to standby.
The Kerys remains in ”AUTO” mode
Manual operation of generating set
This mode of operation is selected with the “MANU” key (on the front of the MMI module). The operator is able to start and stop the
generating set by using the MMI keypad. The generating set power unit is switched off by means of the MMI keys. The safety devices
of the generating set remain active in this mode of operation.
This mode of operation is the responsibility of the operator.
68/297
Summary of Contents for R570U
Page 1: ...User and maintenance manual for generating sets R570U 33504081501NE_1_1 ...
Page 15: ...Alternator Cabinet Figure 1 3 Examples of identification plates 13 297 ...
Page 18: ...Sockets voltage 208 120V 16 297 ...
Page 125: ...9 Appendix 9 1 Appendix A Engine user and maintenance manual 123 297 ...
Page 126: ...124 297 ...
Page 128: ...126 297 ...
Page 129: ...OPERATOR S MANUAL Generating set and industrial engines 16 liter EMS 2 127 297 ...
Page 159: ...157 297 ...
Page 218: ...216 297 ...
Page 220: ...218 297 ...
Page 222: ...7748681 English 12 2011 220 297 ...
Page 223: ...9 2 Appendix B Alternator user and maintenance manual 221 297 ...
Page 224: ...222 297 ...
Page 226: ...224 297 ...
Page 250: ...www leroy somer com 248 297 ...
Page 261: ...Installation and maintenance R250 A V R 4067 en 2009 05 b LEROY SOMER 11 259 297 ...
Page 281: ...2012 03 e LEROY SOMER 19 Installation and maintenance R 450 AVRs 4531 en 279 297 ...
Page 282: ...www leroy somer com 280 297 ...