3 - INSTALLATION
Personnel undertaking the various
operations indicated in this section must
wear personal protective equipment
appropriate for mechanical and electri-
cal hazards.
3.1 - Assembly
All mechanical handling operations
must be undertaken using suitable
equipment and the machine must be
horizontal. Check how much the machine
weighs (see 4.8.3.) before choosing the
lifting tool.
3.1.1 - Handling
The generously-sized lifting rings are for
handling the alternator alone. They must not
be used to lift the genset. The choice of
lifting hooks or handles should be determined
by the shape of these rings. Choose a lifting
system which respects the integrity and the
environment of the alternators.
During this operation, do not allow
anyone to stand under the load.
3.1.2 - Coupling
3.1.2.1 - Single-bearing alternator
Before coupling the machines, check that
they are compatible by:
- undertaking a torsional analysis of the
transmission,
- checking the dimensions of the flywheel
and its housing, the flange, coupling discs
and offset.
When coupling the alternator to the
prime mover, do not use the fan to turn
the alternator or rotor.
The holes of the coupling discs should
be aligned with the flywheel holes by
cranking the engine.
Make sure the alternator is securely
bedded in position during coupling.
Check that there is lateral play on the
crankshaft.
3.1.2.2 - Double-bearing alternator
- Semi-flexible coupling
Careful alignment of the machines is
recommended, checking that the lack of
concentricity and parallelism of both parts
of the coupling do not exceed 0.1 mm.
This alternator has been balanced with a
1/2 key.
3.1.3 - Location
The room where the alternator is placed
must be ventilated to ensure that the
ambient temperature cannot exceed the
data on the nameplate.
3.2 - Checks prior to first use
3.2.1 - Electrical checks
Under no circumstances should an
alternator, new or otherwise, be operated
if the insulation is less than 1 megohm
for the stator and 100,000 ohms for the
other windings.
WARNING
230/297
Summary of Contents for R570U
Page 1: ...User and maintenance manual for generating sets R570U 33504081501NE_1_1 ...
Page 15: ...Alternator Cabinet Figure 1 3 Examples of identification plates 13 297 ...
Page 18: ...Sockets voltage 208 120V 16 297 ...
Page 125: ...9 Appendix 9 1 Appendix A Engine user and maintenance manual 123 297 ...
Page 126: ...124 297 ...
Page 128: ...126 297 ...
Page 129: ...OPERATOR S MANUAL Generating set and industrial engines 16 liter EMS 2 127 297 ...
Page 159: ...157 297 ...
Page 218: ...216 297 ...
Page 220: ...218 297 ...
Page 222: ...7748681 English 12 2011 220 297 ...
Page 223: ...9 2 Appendix B Alternator user and maintenance manual 221 297 ...
Page 224: ...222 297 ...
Page 226: ...224 297 ...
Page 250: ...www leroy somer com 248 297 ...
Page 261: ...Installation and maintenance R250 A V R 4067 en 2009 05 b LEROY SOMER 11 259 297 ...
Page 281: ...2012 03 e LEROY SOMER 19 Installation and maintenance R 450 AVRs 4531 en 279 297 ...
Page 282: ...www leroy somer com 280 297 ...