OPEN
The TRIP output relay closes in response to the OPEN command. The TRIP relay remains
closed until the overcurrent elements in Relay Word row 1 have dropped out. In all cases the
TRIP output remains asserted at least TDUR cycles. If TDUR=0, the OPEN command is
aborted.
To open the power circuit breaker by command, type
OPEN <ENTER>.
The prompt
"
Open BREAKER (Y/N)?
"
is transmitted. Answering
Y <ENTER>
yields a second
prompt:
"
Are you Sure (Y/N)?
"
. Answering
Y <ENTER>
again causes the TRIP output
relay to close as described above. Answering
N <ENTER>
to either prompt aborts the
OPEN command with the message
"
Aborted
"
.
The OPEN command aborts unless the remote open/close jumper (JMP104) is in place on the
main circuit board.
PASSWORD (1 or 2) password
PASSWORD allows you to inspect or change existing passwords. To inspect passwords, type
PASSWORD <ENTER>
as the following example shows:
Date Code 920326
Commands and Serial Communication
SEL-267D/167D Instruction Manual
3-19