When relay power is turned on, the LED display indicates the functions marked on the front
panel. The LEDs default to displaying fault information shown in the RELAY TARGETS
row of the following table.
Using the TARGET command, you may select any one of seven sets of data listed below to
be printed and displayed on the front panel LEDs.
LED: 1
2
3
4
5
6
7
8
n
O
P H l
G l
P H 2
G 2
PH3
G3
51P
51N
Relay Targets
1
51NP
5ONl
50N2
50N3
51PP
5OPl
50P2
50P3
Relay Word Row #l
2
DFP
6 7 N l
67N2
67N3
DFG
6 7 P l
67P267P3
Relay Word Row #2
3
51NT
Z l G T
Z2 GT
Z3GT
51PT
Z l P T
Z2PT
Z3PT
Relay Word Row #3
4
ALRM TRIP
T C
D T
52BT
52AT
TOCP
DCTH
Relay Word Row #4
5
52AT
.
E T
52A
D C
B T
P T
DT
Contact Inputs
6
.
TRIP
CLOS
A l
A2
A3
A 4
ALRM
Contact Outputs
Table 3.2: Target LED Assignment
These selections are useful in testing, checking contact states, and remotely reading targets.
"
1
"
indicates an asserted element;
"
0
"
indicates an deasserted element.
The ALRM (ALARM) bit in target 4 (RELAY WORD ROW #4) and target 6 (CONTACT
OUTPUTS) asserts for the ACCESS command, 2ACCESS command, and self test failures. It
does not assert for the SET, LOGIC, PASSWORD, and DATE commands. This differs from
the ALARM output relay, which asserts for all the above conditions.
The optional command parameter k selects the number of times the target data are repeatedly
displayed for a given choice of parameter n. To see a series of ten readings of Relay Word
Row #4, type
TARGET 4 10 <ENTER>.
Be sure to return the target function to display the fault targets, so field personnel do not
misinterpret the displayed data. The TAR 0 command displays fault targets.
Pressing the TARGET RESET button on the front panel clears the TAR 0 data and lights all
target LEDs for approximately one second as a lamp test when no TRIP condition is present.
Further, pressing the TARGET RESET button unlatches the TRIP output when no TRIP
condition is present. This feature is useful during relay testing and minimizes the risk of re-
installing the relay with the TRIP output asserted. The lamp test fails if the relay is disabled
due to a self test failure. If a TRIP condition is present when you press the TARGET RESET
button, the relay does not unlatch the TRIP outputs or clear the targets.
Date Code 940512
Commands and Serial Communication
SEL-267D/167D Instruction Manual
3-15
Summary of Contents for SEL-167D
Page 3: ......
Page 6: ......
Page 8: ......
Page 9: ......
Page 10: ......
Page 11: ......
Page 51: ...LOGIC DIAGRAMS Date Code 920326 Specifications SEL 267D 167D Instruction Manual 2 31 ...
Page 52: ...Date Code 920326 Specifications 2 32 SEL 267D 167D Instruction Manual ...
Page 53: ...Date Code 920326 Specifications SEL 267D 167D Instruction Manual 2 33 ...
Page 54: ...Date Code 920326 Specifications SEL 267D 167D Instruction Manual 2 34 ...
Page 88: ...SAMPLE EVENT REPORT ...
Page 114: ......
Page 115: ......