INPUTS
DT :
DIRECT TRIP input
PT :
PERMISSIVE TRIP input
BT :
BLOCK TRIP input
DC :
DIRECT CLOSE input
52A :
BREAKER AUXILIARY 52A SWITCH input
ET :
EXTERNAL TRIGGER (for event report) input
In the example event report, the first element to detect the fault picks up in the third quarter
cycle of the fourth cycle of the event report. This is the low set residual-overcurrent element
(50N3) as indicated by the "3" in the 50N column. For almost every actual fault, the first
element(s) to pick up will be found near the sixteenth row of data.
In the sixteenth row of the report, the Zone 3 phase overcurrent element picks up as indicated
by the "3" in the 50P column. The Zone 2 residual-overcurrent element picks up in the
eighteenth row as indicated by the "2" in the 50N column. In the next quarter cycle, the 67N2
and 67P2 elements pick up, and the A1 programmable output asserts. For the example
settings, the A1 output is programmed to generate an over-reaching permissive signal for a
POTT scheme, and thus asserts as soon as any Zone 2 directional element picks up.
In the nineteenth quarter cycle, the Zone 1 residual-overcurrent element (50N1) picks up. In
response, the TRIP output asserts. The TRIP output asserts because the 50N1 element was
selected in the UNCONDITIONAL TRIP MASK (MTU) of the LOGIC settings.
The 52A contact input monitored the latching relay (circuit breaker simulator) state. This
input de-asserts in the thirty-first row of the report, indicating that the latching relay had
changed to the "open" state 3.25 cycles after tripping was initiated.
The duration of the fault can be estimated from the total time the relay elements are picked
up. They were picked up for a total of nineteen quarter cycles, or 5.75 cycles. This value is
reported near the bottom of the report as: Duration: 5.75.
For further description of information in this report, see the HISTORY command description.
4-6
Event Reporting
SEL-267D/167D Instruction Manual
Date Code 920326
Summary of Contents for SEL-167D
Page 3: ......
Page 6: ......
Page 8: ......
Page 9: ......
Page 10: ......
Page 11: ......
Page 51: ...LOGIC DIAGRAMS Date Code 920326 Specifications SEL 267D 167D Instruction Manual 2 31 ...
Page 52: ...Date Code 920326 Specifications 2 32 SEL 267D 167D Instruction Manual ...
Page 53: ...Date Code 920326 Specifications SEL 267D 167D Instruction Manual 2 33 ...
Page 54: ...Date Code 920326 Specifications SEL 267D 167D Instruction Manual 2 34 ...
Page 88: ...SAMPLE EVENT REPORT ...
Page 114: ......
Page 115: ......