The Programmable Trip Logic is shown in Figure 2.2.
THIS LOGIC REPEATS FOR EACH BIT IN RELAY WORD
Figure 2.2: Programmable Trip Logic Diagram
The general form for each output equation follows:
Let R =
Relay Word
M T U =
mask for trip (unconditional)
M P T =
mask for trip (permissive trip)
M T B =
mask for trip (with no blocking)
M T O =
mask for trip (with breaker open)
Then:
TRIP
= R * MTU
+ R * MPT * PT
+ R * MTB * NOT (BT)
+ R * MTO *
52BT
close
TRIP
contact
=
TRIP
open
TRIP
contact
=
NOT
(TRIP)
* [NOT(Any element in Relay Word Row 1 picked
up) + (TARGET RESET button pushed] * Trip Duration timer
expired (TDUR)]
close CLOSE contact =
(DC + 79OI1 + 79OI2 + 79OI3 + CLOSE command) * NOT
(52A)
open CLOSE contact
=
NOT (CLOSE) + 79RS
Al = R * MA1
A2 = R * MA2
A3 = R * MA3
A4 = R * MA4
The
"
*
"
symbol indicates logical
"
and
"
, while the
"
+
"
indicates logical
"
or
"
.