1 .
All commands received by the relay must be of the form:
<command><CR>
or
<command><CRLF>
Thus, a command transmitted to the SEL-267D relay should consist of the command
name, followed by either a carriage return or a carriage return and a line feed. When
entering commands, you may truncate to the first three characters. Upper or lower cases
are irrelevant for all command entries except passwords.
2.
All messages transmitted by the relay are of the following format:
<STX> <MESSAGE LINE 1> <CRLF>
<MESSAGE LINE 2> <CRLF>
<LAST MESSAGE LINE> <CRLF> <PROMPT> <ETX>
That is, each message begins with the start-of-transmission character (ASCII 02), and
ends with the end-of-transmission character (ASCII 03), and each line of the message
includes a carriage return and line feed at its end.
Note:
The ENTER key on most key boards is configured to send the ASCII character
13 (ˆM) for a carriage return. This manual instructs you to press the ENTER
key after commands, which should send the proper ASCII code to the relay.
3.
The relay indicates the volume of data in its received-data buffer by an XON/XOFF
protocol.
XON (ASCII hex 11) is transmitted by the relay when the buffer drops below ¼ full.
The relay also asserts the RTS output.
XOFF (ASCII hex 13) is transmitted when the buffer fills above 3/4 full. The relay
deasserts the RTS output when the buffer is approximately 95% full. Automatic
transmitting sources should monitor for the XOFF character and suspend transmission so
that they won’t overwrite the buffer. Transmission should resume when the XON
character is received.
4.
An XON/XOFF procedure may be used to control data transmission by the relay. When
the relay receives XOFF while transmitting, it pauses until an XON character is received.
If no message is being transmitted when XOFF is received, the relay blocks transmission
of any message presented to its transmitting buffer. The message will be transmitted
when XON is received.
Reception of the CAN character (ASCII hex 18) aborts a pending transmission. This is
useful in terminating unwanted transmissions.
Date Code 920326
Commands and Serial Communication
SEL-267D/167D Instruction Manual
3-3
.
.
Summary of Contents for SEL-167D
Page 3: ......
Page 6: ......
Page 8: ......
Page 9: ......
Page 10: ......
Page 11: ......
Page 51: ...LOGIC DIAGRAMS Date Code 920326 Specifications SEL 267D 167D Instruction Manual 2 31 ...
Page 52: ...Date Code 920326 Specifications 2 32 SEL 267D 167D Instruction Manual ...
Page 53: ...Date Code 920326 Specifications SEL 267D 167D Instruction Manual 2 33 ...
Page 54: ...Date Code 920326 Specifications SEL 267D 167D Instruction Manual 2 34 ...
Page 88: ...SAMPLE EVENT REPORT ...
Page 114: ......
Page 115: ......