SERIAL PORT CONNECTIONS AND CONFIGURATIONS
visible near the center of the relay drawout assembly, to the right of the target LEDs.
Caution:
The SEL-267D relay is equipped with two EIA RS-232-C serial communications ports.
PORT 2 has 9-pin connectors on both the front and rear panels, designated PORT 2F and
PORT 2R, respectively.
PORT 2R, located on the relay rear panel, is typically used with an SEL-DTA Display/-
Transducer Adapter, SEL-RD Relay Display, or local printer. PORT 2F is always available
for short term local communications with a portable computer or printing terminal. Simply
plug the device into the front panel port. The relay automatically discontinues communica-
tions with PORT 2R and addresses PORT 2F. When testing or data retrieval is complete,
unplug the temporary device from PORT 2F. The relay automatically resumes communica-
tion with the device connected to PORT 2R.
Serial communications PORT 1 and the Auxiliary Input for demodulated IRIG-B time code
input remain on the relay rear panel.
Communications port baud rate jumpers are located along the front edge of the circuit board.
To select a baud rate for PORT 1 or PORT 2, remove the relay front panel. The jumpers are
Carefully move the jumpers using needle-nosed pliers. Available rates are 300, 600, 1200,
2400, 4800, and 9600 baud.
Do not select two baud rates for the same port as this can damage the relay
baud rate generator. The relay is shipped with PORT 1 set to 300 baud and
PORT 2F/2R set to 2400 baud.
The SEL-167D relay does not include a front Panel connector for PORT 2.
The serial data format is:
Eight data bits
Two stop bits
No parity bit
This format cannot be altered.
COMMUNICATIONS PROTOCOL
Communications protocol consists of hardware and software features. Hardware protocol
includes the control line functions described above. This section also describes a software
protocol designed for manual and automatic communications.
3-2
Commands and Serial Communication
SEL-267D/167D Instruction Manual
Date Code 920326
Summary of Contents for SEL-167D
Page 3: ......
Page 6: ......
Page 8: ......
Page 9: ......
Page 10: ......
Page 11: ......
Page 51: ...LOGIC DIAGRAMS Date Code 920326 Specifications SEL 267D 167D Instruction Manual 2 31 ...
Page 52: ...Date Code 920326 Specifications 2 32 SEL 267D 167D Instruction Manual ...
Page 53: ...Date Code 920326 Specifications SEL 267D 167D Instruction Manual 2 33 ...
Page 54: ...Date Code 920326 Specifications SEL 267D 167D Instruction Manual 2 34 ...
Page 88: ...SAMPLE EVENT REPORT ...
Page 114: ......
Page 115: ......