Operating Temp.
Burn-in Temp.
Directional
Overcurrent
Protection for
Phase Faults
Directional
Residual-Overcurrent
Protection for
Ground Faults
Automatic Reclosing
Fault Location
Metering
Event
Reporting
-40°F to 158°F (-40°C to 70°C)
Each relay is burned in at 60°C for 100 hours
Nine phase overcurrent elements in three groups
Three timers, one per group
Polyphase time-overcurrent element with selectable curve shapes
Phase directional element operates from negative-sequence and positive-
sequence quantities. The negative-sequence voltamperes are weighted four
times the positive-sequence voltamperes.
Three definite-time elements
One time-overcurrent element with selectable curve shapes
Negative- and zero-sequence directional elements for ground faults.
For selectable fault types (3 shots)
Fault location is computed using event reports stored following each fault. The
algorithm compensates for prefault current, improving accuracy for high-
resistance faults.
All metered quantities are displayed in primary units.
Voltage:
Phase-phase voltages are measured, scaled to primary and
displayed upon command.
Each phase current is measured, scaled to primary and displayed
on command. Calculated phase-to-phase currents are also
displayed.
Current demand is computed with a 5 to 60 minute time constant.
To see the current demand issue a METER command. Peak
demand is determined and stored, and is resettable by command.
A demand threshold setting is provided. When the demand
exceeds the setting, the DCTH bit in the Relay Word is set. It
can be used for tripping, annunciation, alarm, etc.
Current:
Demand:
Power:
MW and MVAR are calculated and displayed on command.
The relay retains a data record with current, voltage, relay element, and
input/output contact information for each of the 12 most recent faults. The
report may also be triggered by command or contact closure. When tripping
occurs after the end of the event report, a second report is triggered at tripping.
2-2
Specifications
SEL-267D/167D Instruction Manual
Date Code 920326
Summary of Contents for SEL-167D
Page 3: ......
Page 6: ......
Page 8: ......
Page 9: ......
Page 10: ......
Page 11: ......
Page 51: ...LOGIC DIAGRAMS Date Code 920326 Specifications SEL 267D 167D Instruction Manual 2 31 ...
Page 52: ...Date Code 920326 Specifications 2 32 SEL 267D 167D Instruction Manual ...
Page 53: ...Date Code 920326 Specifications SEL 267D 167D Instruction Manual 2 33 ...
Page 54: ...Date Code 920326 Specifications SEL 267D 167D Instruction Manual 2 34 ...
Page 88: ...SAMPLE EVENT REPORT ...
Page 114: ......
Page 115: ......