6.5. Connecting the compressed air supply
The customer must provide a compressed air supply at a quality in accordance with ISO
8573-1:2010
– 6-4-4 and install it up to the oil mist detector.
ATTENTION!
Premature contamination of the light path
The device may trigger a premature error message
➔
Comply with the quality requirements for compressed air.
The connection to the filter control valve of the oil mist detector is via interface P1 (see
Figure 11).
Figure 11: Direction of flow of compressed air at filter control valve (273456)
P1
Pipe diameter
10mm (L10)
Thread for union nut
M16x1.5
Compressed air supply, min.
2 bar
Compressed air supply, max.
14 bar
WARNING!
Risk of injury from whipping of the connecting hose line
Minor to severe bruises
➔
Check the applied system pressure before connecting the supply pressure.
P1