Operating manual for the VISATRON VN2020
V2.0 12/2021 EN
Page
79
of
106
SCHALLER AUTOMATION
66440 Blieskastel / Saarland / Germany / Industriering 14 / P.O. Box 1280
Industrielle Automationstechnik GmbH & Co. KG
T
el. +49(0)6842-508
-
0
/ Fax -260 / Email: [email protected] /
www.schaller-automation.com
7.
Figure 134: Release pressure in the filter
control valve
8.
Figure 135: Set negative pressure
Release pressure in the filter control
valve. To do so, screw the blue cap
anticlockwise all the way out.
Switch on the compressed air supply to
the oil mist detector.
Set the negative pressure on the
measuring head (see Section 7.10.1).