8. Operation and application
8.1. Display and alarm reset
If the oil mist concentration is high, the LED indicator will increase and at 70% opacity of the
set alarm threshold, the
“Oil Mist Alarm” LED comes on. At 100% opacity relative to the set
alarm threshold, the
“Oil Mist Alarm” LED will start flashing. If the opacity subsequently
decreases, the alarm status is saved.
Figure 62: Example LED display with alarm
The opacity is displayed on the LED level indicator on the right. If the top LED comes on, the
opacity has reached/exceeded the oil mist alarm threshold.
If an oil mist alarm is triggered, the alarm on the oil mist detector must be cancelled manually
(Figure
➔
Only reset the oil mist detector via the reset button if you have previously made sure
that there is no high oil mist concentration left in the crankcase or as soon as the oil
mist concentration is below the displayed alarm limit.
DANGER!
Risk of explosion due to oil mist.
Severe to fatal injuries.
➔
If an oil mist alarm occurs, do not approach the engine again until the oil mist
concentration on the LED level indicator on the VN2020 or the remote display has
dropped to 0%.
Light
comes
on
Light
comes
on
Light
comes on /
Step II