102
*
P2.12
Reference signal for homing
Default value
0
Setting range
0: Home position LS
1: +OT
2:
−OT
If the encoder Z-phase is selected as a reference signal for shift operation, specify the timing signal for
deceleration to the creep speed for homing. The first encoder Z-phase after reference signal for shift
operation detection is the starting point of the home position shift unit amount.
−OT
+OT
Home position LS
Homing speed
Homing creeping
speed
Speed
Time
Home position LS
OFF
ON
OFF
Example where the home
position LS is the reference
signal for homing
*
P2.13
Home position LS signal edge selection
Default value
0
Setting range
0: ON Rising edge
1: OFF Rising edge
Not a compulsory item
Specify the enabling timing of the home position LS signal if the home position LS is specified as a reference
signal for shift operation reference signal for homing.
Homing speed
Homing creeping
speed
Speed
Time
Home position
LS
OFF
ON
OFF
[Home position LS timing selection = 0]
Homing speed
Homing creeping
speed
Speed
Time
Home position
LS
OFF
ON
OFF
[Home position LS timing selection = 1]
P2.14
Home position shift unit amount
Default value
1000
Setting range
0 to 2000000000 [units]
Specify the distance (traveling amount) from the reference signal for shift operation to the home position.
Reference signal for
shift operation
Home position shift unit amount
Home
position