119
P2.64
Torque keeping time to holding brake
Default value
0.00
Setting range
0.00~9.99 [s]
Assign the "brake output (Function NO.14)" signal to the output signal.
The reference value of this parameter indicates the delay taken from shutoff of servo-on (Function NO.1) to
free-run.
Specify a time larger than the one taken from excitation of the brake to actual brake application.
The brake output signal is turned off when servo-on is turned off.
*P2.66
Flying start at speed
control
Default value
0
Setting range
0: No flying start 1: Flying start
The parameter is enabled under speed control.
If servo-on is turned on during free-run operation, the speed at the timing is picked and acceleration begins
at the speed.
The speed at the timing of power-on is not picked in this case.
*P2.67
Alarm detection at undervoltage
Default value
1
Setting range
0: No detection 1: Detection
Select whether or not to detect alarms when undervoltage is detected.
The detected alarms include main power undervoltage.
P2.69
Deviation detection overflow value
Default value
15.0
Setting range
0.1~100.0 [rev]
Specify the value for detecting a "deviation overflow" alarm.
Enter the parameter in a rotation amount of the motor output shaft.
P2.70
Overload warning value
Default value
50
Setting range
10~100 [%]
Specify the output level of the "overload warning (27) signal that is issued as an output signal (EOUT signal).
Use the signal as a warning of an "overload (OL)" alarm.