Sauter flexotron®800
ventilation
Settings
P100012082
76
15.6.1
Alarm limits
Alarm limits, supply air
Al. lim. supply air
Control dev: 10.0 °C
High temp: 30.0 °C
Low temp: 10.0
Alarm limits, extract air
Al. lim. extract air
High temp: 30.0 °C
Low temp: 10.0 °C
Alarm limits, room
Al. lim. room air
High temp: 30.0 °C
Low temp: 10.0 °C
Alarm limit frost protection
Alarm limit frost
protection
7.0 °C
Alarm limit, pressure
Control dev SAF
40.0 Pa
Control dev EAF
40.0 Pa
Alarm limit Humidity
Control deviation
humidity
10 %
Alarm limit, exchanger efficiency
Low efficiency
50.0 %
Service alarm filter
Service alarm
(Filter alarm)
Time until alarm
Activates: 0 month