Sauter flexotron®800
ventilation
About flexotron®800
P100012082
13
Outputs
Analogue outputs AO
................................
Configurable
0…10 V DC; 2…10 V DC;
10…0 V DC or 10…2 V DC, 2 mA
8 bit D/A short-circuit protected
Digital outputs DO
..............................
Mosfet outputs, 24 V AC/DC, 2 A continuous
not short-circuit protected, totally max 8 A.
Options
WEB (TCP/IP-port)
...................................................
Replaces the RS485 Port 1
2-port flexotron®800 models
...
Two serial ports or one serial port and one TCP/IP port
External hand terminal,RDB800
........
For use with flexotron®800 units without display
Position of the terminals on flexotron® 800