Sauter flexotron®800
ventilation
Installation and wiring
P100012082
18
Description
CASE flexotron®
Display
CO
2
sensor, 0…10 V DC
CO2 Sensor
CO2
Pressure transmitter supply air,
0…10 V DC
SAF Pressure
SAF pressure
Pressure transmitter extract air,
0…10 V DC
EAF Pressure
EAF pressure
De-icing sensor, heat exchanger
Deicing Temp
Deicingtemp
Frost protection sensor
Frost Protection Temp
Frost prot.
temp
Room humidity sensor
Humidity Room
Humidity room
Duct humidity sensor
Humidity Duct
Humidity duct
Outdoor humidity sensor
Humidity Outdoor
Humidity out
Temperature sensor, Extra
controller
Extra unit temp
Extra unit
temp
External control supply air fan
External control SAF
SAF ext. Ctrl
External control extract air fan
External control EAF
EAF ext. Ctrl
Pressure transmitter supply air 2
SAF Pressure 2
SAF pressure
2
Intake temperature
Intake Temp
Intaketemp
Extra temperature sensor 1
Extra Sensor Temp 1
Extrasensor
Extra temperature sensor 2
Extra Sensor Temp 2
Extrasensor 2
Extra temperature sensor 3
Extra Sensor Temp 3
Extrasensor 3
Extra temperature sensor 4
Extra Sensor Temp 4
Extrasensor 4
Extra temperature sensor 5
Extra Sensor Temp 5
Extrasensor 5
Extra pressure transmitter supply air Extra SAF Pressure
Extra SAF
Pressure
Extra pressure transmitter extract
air
Extra EAF Pressure
Extra EAF
Pressure
1.1.1.1.1
Digital input signal
Description
CASE flexotron®
Display
Filter guard, supply air
Filter Guard 1
Filter alarm 1
Filter guard, extract air
Filter Guard 2
Filter alarm 2
Run-indication/alarm circulation
pump, Heating
Heat Pump Indication
P1-Heating
Run-indication/alarm circulation
pump, exchanger
Exchange Pump Indication P1-Exchanger
Run-indication/alarm circulation
pump, Cooling
Cooling Pump Indication
P1-Cooling
Fire alarm
Fire Alarm
Fire alarm