Sauter flexotron®800
ventilation
Time settings
P100012082
70
13.4
Extended running
Digital inputs can be used to force the unit to start although the timer says the running
mode should be
‘‘Off’’.
For 2-speed fans and pressure/flow controlled fans, inputs for normal speed and
reduced speed can normally be used.
The unit will run for the set time. If the running time is set to zero the unit will only run as
long as the digital input is closed.
Extended running
60 min
Time in ext. Running
0 min
13.5
Timer outputs 1…5
Up to 5 digital outputs can be used as timer controlled outputs. Each with individual
week-schedules with two activation periods per day. Each output has eight separate
setting menus, one for each weekday and one extra for holidays. Holiday schedules
take precedence over other schedules.
Only the time channels which have been configured, i.e. have been wired to a digital
output, will be shown.
Timer output 2
Wednesday
Per.1: 05:30 – 08:00
Per.2: 17:00 – 23:00
If the function "Recirculation" has been configured (see 5.1.11), "Timer output 5" can be
used to control start/stop of the recirculation function.
13.6
Holidays
Up to 24 separate holiday periods for a full year can be set.
A holiday period can be any number of consecutive days from 1…365. The dates are in
the format: MM:DD.
When the present date falls within a holiday period, the scheduler will use the settings
for the weekday
‘‘Holiday’’.
Holidays (mm:dd)
1: 01-01 – 02-01
2: 09-04 – 12-04
3: 01-05 – 01-05